Part 2 Startup Chapter


(5) RS485SIO

Using the 2-wire method, connnect the Gateway R unit (RG W-SIO) to the RS-422A/485 port on the serial communication
unit (SCU) of the PLC, as shown below.

Gateway R unit

PLC-SCU

RS--422A/485 connector


Cable connector (supplied)

(D-sub 9-pin male connector as

viewed from the soldered side)

MC1.5/4-ST-3.5 (manufactured by

Phoenix Contact)

Use a shielded twisted pair cable (AWG28-16) for the communication cable.

Gateway R unit


Shield


Shell

Caution

1.

The polarities of the communication lines may be the other way around depending on the SCU of PLC.

SA (+) on Gateway R SDB (+) on SCU, SB (-) on Gateway R

SDA (-) on SCU.,

2.

Connect the shield to ground only on the PLC-SCUU end.