Part 1 Specification

Chapter 3 Gateway R unit

93

Part 1 Specification

3.8.3 Basic Operation Timings

(1) Ready

Follow the steps bellow to start the system after confirming that the slider or rod is not contacting a mechanical end and

the transferring load is not contacting any peripherals, either:

[1] Cancel the emergency stop or enable the motor drive power.

[2] Supply the 24-VDC controller power (24-V terminal and 0-V terminal on the power-supply terminal block).

[3] Initialize the minimum parameter(s) required.

(Example) x To change the feed speed during teaching:

Change the value of parameter No. 35, “Safety speed.”

[4] In the positioner mode or simple direct mode, set optimal values in the “Position,” “Speed,” “Acceleration,”

“Deceleration” and other fields of the position table.

Caution

If the power is turned ON while an emergency stop is actuated and then the emergency stop is cancelled (SON signal “1”

(ON)), it will take a maximum of 1.6 seconds after the cancellation of emergency stop for the servo to turn ON.

Emergency stop cancelled

Servo ON

1.6 sec or less

Safety circuit status

Supply of 24-VDC

controller power

Emergency stop cancelled

SV lamp

(front panel)

A steady orange light comes on only for 2 seconds,

and then turns OFF.

Green

Controller ready

(CRDY)

Initial parameter setting

Pause (STP)

Pause cancelled

Servo ON command

(SON)

Ready (SV)

Position complete

(PEND)

1.6 sec or less

“0” (OFF)

-117-