Part 1 Specification

Chapter 3 Gateway R unit

121

Part 1 Specification

(4) Message Frame

Query and response messages use the following message frame.

Header

Address

Function

Data

Error check

Trailer

T1-T2-T3-T4

8 bits

8 bits

N x 8 bits

16 bits

T1-T2-T3-T4

* “T1-T2-T3-T4” represents a silent interval.

[1] Header field

The frame starts with a silent interval of 3.5 characters or more.

[2] Address field

The address in the message frame. Fixed to 3FH for the RS485 SIO gateway.

[3] Function field

The following three functions can be used in the Modbus gateway mode.

Code (Hex)

Name

Function

Broadcast

support

03H

Read Holding Registers

Read holding registers

06H

Preset Single Register

Write holding register

{

10H

Preset Multiple Registers

Write multiple holding registers simultaneously

{

[4] Data field

This field is used to append data relating to the function code. The data field has a variable length and it can be

omitted.

[5] Error check field

16-bit data is indicated by two bytes of eight-bit data.

The error check result is calculated by the method called “CRC (Cyclical Redundancy Check).”

[6] Trailer field

The frame ends with a silent interval of 3.5 characters or more.

-145-