Part 2 Startup Chapter

Chapter 6 Setting for External SIO Link and Other

349

Part 2 Startup Chapter

6.2 Other

Items to note regarding the condition of user setting switch SW1 on the Gateway R unit are given below.

(1) When SW1 = OFF (TP enable switch signal disabled)

The TP enable switch signal of each connected RPCON, RACON, PCON-CF or SCON controller becomes ineffective

regardless of the enable operation parameter set by the gateway parameter tool.

(2) When SW1 = ON (TP enable switch signal enabled)

[1] When the enable operation parameter is set to “Shutdown control”

When the TP enable switch is disabled, each connected RPCON, RACON, PCON-CF or SCON controller stops (the

axis decelerates to a stop o the servo turns off o the drive source is cut off).

[2] When the enable operation parameter is set to “Servo control”

When the TP enable switch is disabled, each connected RPCON or RACON controller stops (the axis decelerates to

a stop o the servo turns off), but each PCON-CF or SCON controller corresponding to an external link axis does not

stop and continues to operate.

The table below summarizes the above information.

Operations when the TP enable switch is enabled

Enable operation set by the parameter setting tool

Shutdown (default)

Servo control

RACON or

RPCON

The axis decelerates to a stop Æ the servo

turns off o the drive source is cut off

(Same as when an emergency stop is

actuated.)

The axis decelerates to a stop o the

servo turns off

Axis operation

when the TP

enable switch

is disabled

External link

axis

The axis decelerates to a stop Æ the servo

turns off o the drive source is cut off

(Same as when an emergency stop is

actuated.)

The axis does not stop (operation

continues). *

Processing by the Gateway

R unit when the TP enable

switch is disabled

x

Drive-source cutoff signal ON o RY2

contacts “Open”

x

Enable signal (disabled state) passed to

the RACON or RPCON controller o

(The controller causes the actuator to

decelerate to a stop and then the servo

turns off). The enable signal is not output

to external link axes.

x

Drive-source cutoff signal OFF o RY2

contacts “Closed”

x

Enable signal (disabled state) passed

to the RACON or RPCON controller o

(The controller causes the actuator to

decelerate to a stop and then the servo

turns off). The enable signal is not

output to external link axes.

* The drive-source cutoff signal of the Gateway R unit remains OFF and the TP enable signal is not output to external link

axes. Accordingly, the operation does not stop even when the TP enable switch is disabled.

Caution

To enable the TP enable operation when external SIO link axes are used, set the enable operation to “Shutdown (default).”

The emergency stop line signal (EMG+, EMG-) is output to external SIO link axes, but the TP enable signal is not output to

these axes.