Part 2 Startup Chapter

Chapter 2 Mounting and Installation

250

Part 2 Startup Chapter

Direction of

air from the

internal fan

Ventilation

2.1.4 Installing in a Control Panel

The ROBONET must be installed using a DIN rail.

Since the ROBONET adopts natural convection cooling, provide a clearance of 50 mm or more above and below the unit, and

100 mm or more in front of the unit, by following the correct installation method explained in 2.1.1. Take note that the above

dimensions do not include wiring space. Increase the clearances by the required wiring space.

The field network cable and emergency-stop circuit cable will be connected to the top and bottom of the Gateway R unit,

respectively. The motor cable and encoder cable will be connected to the bottom of the RPCON or RACON unit, and the

encoder cable will also be connected to the bottom of the simple absolute R unit.