Part 2 startup chapter – IAI America REXT User Manual

Page 330

Advertising
background image

0

Part 2 Startup Chapter

Chapter 5 Network Setup

304

Part 2 Startup Chapter

[3]

Set other parameters as shown below. “Mode Setting” should be set to “Remote Network Version 1 Mode,”

because the master is set as a version 1 remote device station according to the occupancy information

reflecting the settings of ROBONET gateway parameters (refer to 5.2.2 (3), “Setting the operation mode of each

axis”).

The system configuration parameters described in 5.2 are set as follows:

x

“First I/O No.” --- I/O address of the master unit. Set to “0080.”

x

“Total Number of Connected Units” --- Number of remote stations. Set to “1.”

x

“Remote Input (RX) Refresh Device” ---

X100

x

“Remote Output (RY) Refresh Device” ---

Y100

x

“Remote Register (RWr) Refresh Device” ---

D200

x

“Remote Register (RWw) Refresh Device” ---

D100

x

Special Relay (SB) Refresh Device ---

SB80

x

Special Relay (SW) Refresh Device ---

SW80

Assign the buffer memory of the

master station to the internal devices

of the PLC-CPU.

(Desired assignments can be

specified.)

-330-

Advertising
This manual is related to the following products: