Part 1 specification – IAI America REXT User Manual

Page 151

Advertising
background image



Part 1 Specification

Chapter 3 Gateway R unit

127

Part 1 Specification

3.9.3.3 Read Holding Registers (Query using FC = 03H)

This query reads the contents of holding registers in the slave. Broadcast is not supported.

The basic query/response structures and examples of queries are shown below.

(1) Basic Query/Response Structures

[1] Query format

The query message specifies the address of the holding register (gateway register) from which to start reading data,

and the number of registers.

Data length of 1 holding register = 1 word = 2 bytes = 16 bits

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

03 H

1

Starting address

(upper)

Arbitrary

Starting address

(lower)

Arbitrary

2

The address varies depending on the axis

arrangement.

Number of registers (upper)

Arbitrary

Number of registers (lower)

Arbitrary

2

Refer to the query list.

Error check

CRC (16 bits)

2

Trailer

None

-

Total bytes

8

[2] Response format

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

03 H

1

Data bytes

Arbitrary

1

Number of registers specified in the query

format x 2

Data 1

(upper)

Arbitrary

Data 1

(lower)

Arbitrary

1 each for upper

and lower words

2

Data 2

(upper)

Arbitrary

Data 2

(lower)

Arbitrary

Same as above










Data corresponding to the data bytes (number

of specified registers x 2)

Error check

CRC (16 bits)

2

Trailer

None

-

Total bytes

-151-