Part 1 Specification

Chapter 3 Gateway R unit

92

Part 1 Specification

(22) Current position number signals (PE0 to PE6) [Solenoid valve mode 1] PLC input signal

When positioning is complete, a signal for the position number corresponding to the movement command (0 to 6) is

output separately.

Correspondence table of output signals and completed positions

Output signal

Completed position

PE0

Position No. 0

PE1

Position No. 1

PE2

Position No. 2

PE3

Position No. 3

PE4

Position No. 4

PE5

Position No. 5

PE6

Position No. 6

Note) These signals turn OFF when the servo turns OFF or an emergency stop is executed. If the actuator is inside the

positioning band relative to the target position when the servo turns ON again, each current position number signal

will turn ON again. If the actuator is outside the positioning band, however, the signal will remain OFF.

(23) Position detection output (LS0 to LS2) [Solenoid volume mode 2] PLC input signal

Similar to the air cylinder LS system, these signals turn ON when the current position is inside the positioning band

relative to each target position.

(Note) Even when the servo turns OFF or an emergency stop is executed while the actuator is stopped at the target position,

the applicable current position number signal will remain ON as long as the actuator is inside the positioning band.

Output signal

Position detection

Remarks

LS0

Rear end position The detection position is defined in the “Position” and

“Positioning band” fields for position No. 0.

LS1

Front end position The detection position is defined in the “Position” and

“Positioning band” fields for position No. 1.

LS2

Intermediate position The detection position is defined in the “Position” and

“Positioning band” fields for position No. 2.