Part 3 maintenance – IAI America REXT User Manual

Page 401

Advertising
background image



Part 3 Maintenance

Chapter 1 T

roubleshooting

369

Part 3 Maintenance

Code

Message

Description

20C CSTR-ON during

operation

This message indicates that a start command signal (CSTR) was changed to “1”

by the PLC while the actuator was moving, and that duplicate movement

commands occurred as a result.

20E Soft limit over

This message indicates that a soft limit was reached.

210

HOME-ON during

operation

This message indicates that the home return signal (HOME) was changed to “1” by

the PLC while the actuator was moving, and that duplicate movement commands

occurred as a result.

221

Write prohibited in

monitor mode

This message indicates that an attempt was made to write position table data or

parameter in the monitor mode.

223

Operation prohibited n

monitor mode

This message indicates that an attempt was made to move the actuator in the

monitor mode.

301

Overrun error (M)

302

Framing error (M)

304

SCIR-QUE OV (M)

305

SCIS-QUE OV (M)

306

R-BF OV

308

Response timeout (M)

30A Packet R-QUE OV
30B Packet S-QUE OV

These messages indicate that an error occurred during serial communication with

the controller.

Cause: [1] Garbage data due to the effect of noise

[2] Duplicate slave station numbers when multiple controllers are

controlled by serial communication

Action: [1] Adjust the wiring in a manner eliminating the effect of noise and

review the installation of equipment, etc.

[2] Change the slave station numbers to avoid duplication.

If the message is still displayed after taking the above actions, please contact IAI.

307

Memory command

denied

This message indicates that a command was denied during serial communication

with the controller.

309

Write address error

This message indicates that an indeterminate WRITE address error occurred

during serial communication with the controller.

These conditions do not occur in normal operations. Should they occur, record the

entire error list before cutting off the power for use in the cause investigation.

Also contact IAI.

30C No connected axis

This message indicates that no controller address is recognized.

Cause: [1] The controller is not operating properly. (power supply error, failure,

etc.)

[2] Only the supplied communication cable (SGA/SGB) is disconnected.

[3] If a SIO converter is used, 24V is supplied to the converter but the

link cable is not connected.

[4] The ADRS switch settings are duplicated by mistake when multiple

controllers are linked.

Action: [1] Check if the RDY lamp on the controller is lit. If the lamp is not lit, the

controller is faulty.

[2] If a spare teaching pendant is available, replace the current pendant

with the spare unit, or with a PC, and see if the message disappears.

[3] Supply the power after connecting the link cable between the

converter and controller.

[4] Make sure the ADRS switch settings are not duplicated.

If the message is still displayed after taking the above actions, please contact IAI.

-401-