Part 1 Specification

Chapter 3 Gateway R unit

86

Part 1 Specification

(10) Pause (STP) PLC Output Signal

Turn this signal “1” (ON), and the axis movement will pause (the axis will decelerate to a stop). Turn the signal “0” (OFF),

and the axis movement will resume.

(11) Command Position Number (PC1 to PC512) PLC Output Signal

The command position number is read as a 10-bit binary number.

Upon detecting the “0” (OFF) o “1” (ON) edge of the CSTR signal, the controller will read the 10-bit binary number

consisting of PC1 to PC512 signals as the command position number.

(12) Completed Position Number (PM1 to PM512) PLC Input Signal

The position complete number is output as a 10-bit binary number.

When the power is turned ON or while the actuator is moving, all of PM1 to PM512 signals are “0” (OFF).

All signals will turn “0” (OFF) once the servo turns OFF or an emergency stop is actuated. The signals will return to “1”

(ON) if the current position is within the positioning band (INP) with respect to the target position when the servo turns

ON again. If the positioning band (INP) is exceeded, the signals will remain “0” (OFF).

These signals also turn “1” (ON) when push operation has completed or the work part has been missed.

(13) Zone (PZONE, ZONE1, ZONE2) PLC Input Signal

These signals remain “1” (ON) while the current actuator position is inside the specified zone.

Zones are set using the position table or user parameters.

This signal becomes effective after completion of home return. It will remain effective, even while the servo is turned off,

once home return has completed.

Setting

Zone signal

Positioner

mode, simple

direct mode

Direct numerical

specification

mode

Solenoid valve mode 1

Solenoid valve mode 2

Individual zone boundaries in the position table

Position zone

output

PZONE

{

X

{

User parameters for zone boundary 1

(Parameter No. 1 = + side, No. 2 = - side)

Zone output 1

ZONE1

{

{

{

User parameters for zone boundary 2

(Parameter No. 23 = + side, No. 24 = - side)

Zone output 2

ZONE2

{

{

X

-108-