Part 2 Startup Chapter

Chapter 2 Mounting and Installation

270

Part 2 Startup Chapter

Teaching pendant

PC, etc.

Do not

connect

the FG.

Do not connect the FG of the PC to ground.

If the FC may be connected to ground

through other COM port, disconnect the

communication cable from the applicable

COM port.

PC software

RS232 connection type

<Model: RCM-101-MW>

USB connection type

<Model: RCM-101-USB>

* The cable is supplied with the PC software.

SIO converter (optional)

(with built-in terminal resistor)

Model: RCB-TU-SIO-A (B)

* One e-CON connector, one junction and one

terminal resistor are supplied with one

controller link cable.

e-CON connector (3-1473562-4 by AMP)
Junction (5-1473574-4 by AMP)

GateWay

R unit

Terminal resistor

Controller link cable

Model: CB-RCB-CTL002

24-V power supply

2.2.9 How to Connect Teaching Tool When Grounding Positive Terminal of 24-V Power

Supply

If the positive terminal of the 24-V power supply is grounded (= the +24-V side is grounded), use a SIO converter as shown

below to connect a teaching pendant or PC to the Gateway R unit. At this time, do not connect the FG of the SIO converter.

With the ROBONET, basically the negative terminal of the 24-V power supply is grounded (= the 0-V side is grounded).

Since most teaching pendants and PCs have their communication ground line and FG (frame ground) shorted internally,

grounding the 24-V power supply at the positive terminal (= grounding the +24-V side) will cause the 24-V power supply to

short when a teaching pendant or PC is connected to the Gateway R unit, resulting in damage to the teaching pendant or PC.

Caution

Do not connect the FG of the SIO converter.

-296-