Part 3 Maintenance

Chapter 2 Maintenance/Inspection

372

Part 3 Maintenance

No. Inspection item

Description

Judgment criterion

Action

4 Connection

condition

Loose wiring connectors

(motor cable, encoder cable,

field network cable,

emergency-stop circuit)

Not loose.

Insert the connector again until it is

locked.

Note) The encoder cable connector is

not locked, so insert the cable

again all the way until it stops.

Broken wiring cables

No exterior

abnormality.

Visually check each cable and replace it

if necessary.

5 Air-cooling fan Operation of the internal

air-cooling fan in the upper

section of the controller unit

(visual check)

Operating.

Replace the controller unit.

6 Backup battery Expiration or consumption of

the backup battery (AB-7) for

simple absolute R unit

The battery lasts for

three years. The

expiration date

specified on the

expiration date label

attached on the

battery has not

passed.

Replace the backup battery if the

expiration date has passed, even when

the battery is not faulty.

2.2 Important Information on Unit Replacement

If any of the units comprising the ROBONET system exhibits abnormality and the unit must be replaced, take heed of the

following points:

x

Replace the unit with the power turned off.

x

After the replacement, check the new unit for abnormality.

x

When sending the defective unit to IAI for repair, attach a piece of paper to the unit describing the abnormal condition as

specifically as possible.

x

Back up the position data, parameters, PLC data and other necessary data in case the data is lost.

-404-