Part 1 Specification

Chapter 3 Gateway R unit

139

Part 1 Specification

(2) Examples of Queries/Responses

Queries are implemented by changing (writing) a 1-word register and thus the basic pattern is the same with all queries.

The only differences are the starting address and data. The following explanations use axis (0) or axis (12) in the

example.

[1] Write gateway control signals 0, 1

MON (bit 15 of control signal 0) is the only applicable control signal. Always turn this signal ON to enable the

applicable control.

z

Query

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

06 H

1

Starting address

(upper)

F6 H

Starting address

(lower)

00 H

2

Address of gateway control signal 0 register

New data (data written) (upper)

80 H

New data (data written) (lower)

00 H

2

Error check

(CRC)

16 bits

2

Based on calculation result

Trailer

None

-

Total bytes

8

z

Response

If the data has been changed (written) successfully, the response is the same as the query.

z

Actual Example

„

Sent Query:

3F06F6008000DF5C

„

Received Response: 3F06F6008000DF5C

-163-