Part 2 Startup Chapter

Chapter 2 Mounting and Installation

264

Part 2 Startup Chapter

2.2.8 Network Wiring

(1) CC-Link

Check the operation manual for the master (PLC) for details on CC-Link. The following explains the points to note

regarding network wiring.

An example of network connection is shown below.

[1]

An equipment connected via CC-Link is called a “station,” and 1 to 64 can be set as slave station numbers. Both

master and slave stations can be set in any positions.

[2]

Each station is connected based on direct line branching at the station. T-branches using commercial terminal

blocks, etc., are also supported.

[3]

Use a dedicated 3-core shielded twisted pair cable for CC-Link.

The details of the dedicated cable are as follows.

Color

Signal type

Blue

Communication line A (DA)

White Communication line B (DB)

Yellow Communication ground line (DG)

---

Shield (SLD)

[4]

A terminal resistor must be installed on both ends of the CC-Link system. Each terminal resistor is connected

between “DA” and “DB.” Take note that the required terminal resistor varies depending on the applicable cable,

as shown below.

Cable name

Terminal resistor

Dedicated CC-Link cable (ver. 1.00, ver. 1.10)

110 :, 1/2 W

Dedicated high-performance CC-Link cable (ver. 1.00)

130 :, 1/2 W

[5]

The baud rate is limited by the length of the network (total branch line length, maximum network length).

Terminal

resistor

Master station

Slave station

Slave station

Terminal

resistor

Dedicated CC-Link cable

(Blue)

(White)

(Yellow)

Dedicated CC-Link cable

-288-