Part 1 Specification

Chapter 3 Gateway R unit

119

Part 1 Specification

3.9.2 Modbus/RTU Protocol Specification

The RS485 SIO Gateway R unit has an asynchronous serial bus interface conforming to EIA RS485 for interfacing with the

host.

The Modbus protocol is used for communication to receive commands from the host or reference internal information in the

host.

The Modbus protocol is a communication protocol developed by Modicon Inc. (AEG Schneider Automation International

S.A.S.) for PLCs, and its specification is open to the world. For the detailed specifications of this protocol, refer to the

specification document (Modbus Application Protocol Specification V1.1a) published by Modbus-IDA

(

http://www.modbus-ida.org/

), along with this specification.

(1) Basic Specifications

The basic specifications were explained in 3.4.4. Key items are summarized below.

Item

Method/condition

Interface

Conforming to EIA RS485

Communication method

Half-duplex communication

Synchronization method

Asynchronous method

Connection pattern

1:1 differential connection

Transmission mode

Modbus/RTU

Baud rate (bps)

Selectable from the following by a parameter:

9600, 19200, 38400,

57600, 115200, 230400

Bit length

8 bits

Stop bit

1 bit

Parity

None

Caution

In the SIO through mode, 9600 bps and 19200 bps cannot be selected.

-143-