Part 1 Specification

Chapter 3 Gateway R unit

113

Part 1 Specification

(5) Operation by Relative Coordinate Specification

The target position in the position table can also be specified in relative coordinates. This function can be used to repeat

positioning operations at equal pitches.

[1] Example of operation in the positioner 1, 2 mode

The following explains an example of positioning operation repeated at a 50-mm pitch, starting from position No. 1.

The position table shown below is created. End of operation is determined based on the count managed by the PLC.

The zone signal can be used to doubly confirm that operation has ended.

Example of Position Table

Position 1

50-mm

pitch

Direction of front end

Last load

Zone output signal

The coordinate immediately before the last load is set as the + boundary.

Position

Zone+

Zone-

Incremental

Comment

On the teaching pendant, this sign indicates that the position is specified in relative coordinates.