Part 1 specification – IAI America REXT User Manual

Page 185

Advertising
background image



Part 1 Specification

Chapter 3 Gateway R unit

161

Part 1 Specification

[2] Query format for normal operation where only the position is changed

Use the same format in [1] by changing only the position data, to operate the axis.

z

Query

Field name

RTU mode data

(8 bits)

Data length

(bytes)

Remarks

Header

None

-

Slave address

3F H

1

Fixed.

Function code

10 H

1

Starting address

(upper)

F6 H

Starting address

(lower)

0C H

2

Initial control signal register address of axis (1)

Number of registers

(upper)

00 H

Number of registers

(lower)

02 H

2

The number of registers is “2” corresponding to

new data 1 to 2.

Bytes

04 H

1

Number of registers x 2 = 4 (04 H)

New data 1

(upper)

03 H

New data 1

(lower)

E8 H

1 each for upper

and lower words

2

New data 2

(upper)

00 H

New data 2

(lower)

00 H

1 each for upper

and lower words

2

Position data specification

10.00 mm = 1000 = 000003E8 H

Error check

(CRC)

16 bits

2

Based on calculation result

Trailer

None

-

Total bytes

13

„

Sent Query:

3F10F60C00020403E80000976C

„

Received Response: 3F10F60C0002B69D

Thereafter, turn the CSTR signal from “0” to “1.”

-185-