9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Possible settings via DIP switches

6.2

Possible settings via DIP switches

The front panel DIP switches of the memory module serve to set the baud rate and the

node address:

[6-1]

DIP switches

6.2.1

Setting the node address

The node address can be set via code

C00350

or via the DIP switches 1 ... 64.

The labelling on the housing corresponds to the values of the individual DIP switches

for setting the node address.

Valid address range: 1 … 127

Example: setting node address 23

Tip!
The node address resulting from the setting of the DIP switches at the last mains

switching is displayed in

C00349/1

.

Baud

CAN Address

O

N

c

d

b

a

64

32

16

8

4

2

1

Note!

• The addresses of the nodes must differ from each other.
• All twelve DIP switches = OFF (Lenze setting):

– On switching on, the settings of codes

C00350

(node address) and

C00351

(baud rate) are active.

• Switch off the voltage supply of the standard device and then on again to

activate changed settings.

DIP switch

64

32

16

8

4

2

1

Switch position

OFF

OFF

ON

OFF

ON

ON

ON

Value

0

0

16

0

4

2

1

Node address

= sum of all values = 16 + 4 + 2 + 1 = 23