Lenze E94ARNE Regenerative power supply User Manual

Page 85

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

85

9400 regenerative power supply module | Parameter setting

Device interface

Automatic restart after power-on/trouble/fault

Auto-start option 0: auto-restart inhibited after power-on
If auto-start option 0 has been selected, the controller inhibit must be explicitly set after

power-on or after resetting a "Trouble" or "Fault" in order that the state of the regenerative

power supply module changes from "Device is ready to switch on" to "Device is switched

on". The subsequent change to the "Operation" state takes place when the controller is

enabled:

[4-13] State change when auto-restart is inhibited (C00142 = "0: Inhibited")


Pulses of the regenerative power supply module are inhibited

Pulses of the regenerative power supply module are enabled


With controller inhibit at power-on

Without controller inhibit at power-on

RFR

Œ

0

1

RFR

RFR

RFR

t

t



Initialisation

Switched on

Operation

Ready to switch on

Initialisation

Switched on

Operation

Ready to switch on