EDS94ARNExxxx EN 2.3 - 06/2014

L

163

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

I-1403

Communication parameter for the reception of process data via RPDO4

For the assignment of the data telegram see object

I-1400

.

I-1600

The object I-1600 serves to receive parameter data via the RPDO1.

[6-16] Assignment of the data telegram

IEC 61131 process data words are mapped. Only whole bytes can be mapped (the mapping

entry granularity is 1 byte).

Index:

I-1403

Name:

RPDO4 communication parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by RPDO

0x500 + node ID

0

4294967295 rw

U32

2: Transmission type

254

0

255 rw

U8

3: Inhibit time

-

- (not used for RPDOs)

rw

U16

4: Compatibility entry

-

- (reserved, read or write access results in the error

message 0x06090011)

rw

U8

5: Event timer

-

- (not used for RPDOs)

rw

U16

Subindex

Meaning

Lenze code

1

Identifier RPDO4

• The basic setting corresponds to the "Predefined

Connection Set": identifier = 0x500 + node ID

C00321/4

2

RPDO transmission type according to DS301 V4.02

Transmission type ( 113)

C00323/4

Index:

I-1600

Name:

RPDO1 mapping parameter

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Number of mapped application

objects in PDO

0

0

8 rw

U8

1 ... 8: Application object 1 ... 8

0

0

4294967295 rw

U32

Subindex

Meaning

0

Number of mapped objects

1 ... 8

Mapping entries 1 ... 8 for RPDO1

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 16

Bit 15 ... bit 8

Bit 7 ... bit 0

Index

Subindex

Length