1 parameter data object identifiers, Parameter data object identifiers – Lenze E94ARNE Regenerative power supply User Manual

Page 121

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

121

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Parameter data transfer

6.7.1

Parameter data object identifiers

In the Lenze setting, the identifier for the parameter data objects SDO1 ... SDO10 consists

of a basic identifier and the node address set in

C00350

:

Identifier (COB-ID) = basic identifier + node address (node ID)

In the Lenze setting, the basic identifiers of the SDOs are preset according to the

"Predefined Connection Set" of DS301 V4.02:

Parameter data object

Direction

Basic identifier

From the device

To the device

dec

hex

SDO1

(parameter data channel 1)

1408

580

1536

600

SDO2 ... 10

(parameter data channels 2 ... 10)

Deactivated

Node guarding, heartbeat

1792

700

Boot up

1792

700

Note!

Please observe that the parameter data channels 2 ... 10 are deactivated in the

Lenze setting.
The procedure for activating these parameter data channels is explained in the

description for the parameters

C00372

and

C00373

and in the description for

the implemented CAN object

I-1201

.

Example

( 158)