Position value faulty [0x00910010, Error during initialisation [0x00910011, Block function in wrong mec task [0x00910012 – Lenze E94ARNE Regenerative power supply User Manual

Page 244: Can module (mxi1): bus off [0x009d0000, 0x00910012, 0x009d0000, 0x00920001, 0x00910011, 0x00910010, 0x00920000

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

244

L

EDS94ARNExxxx EN 2.3 - 06/2014

Position value faulty [0x00910010]

Error during initialisation [0x00910011]

Block function in wrong MEC task [0x00910012]

Safety module: Incompatible with setting in C00214 [0x00920000]

Communication with safety module interrupted [0x00920001]

CAN module (MXI1): Bus off [0x009d0000]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

If the error occurs frequently, please contact Lenze.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

If the error occurs frequently, please contact Lenze.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Internal error

If the error occurs frequently, please contact Lenze.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A safety module is inserted in the regenerative power

supply module. The regenerative power supply module

does not support safety engineering.

Use SM0 module (without safety engineering).

• Then, restart the controller.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Communication between the regenerative power supply

module and the safety module cannot be established.

• Switch off regenerative power supply module, insert

SM0 safety module correctly, and switch on the

regenerative power supply module again.

• If the problem occurs again, exchange the SM0 safety

module.

Response (Lenze setting printed in bold)

Setting:

C13595

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: "Bus-off"

state

• Too many faulty telegrams received.

• Defective cable (e.g. loose contact).

• Two nodes with the same ID.

• Eliminate disturbances (e.g. EMC).

• Remove loose contact, screw down adapter.

• Assign different node IDs.