9400 regenerative power supply module | Parameter setting

Commissioning

Short setup

14

L

EDS94ARNExxxx EN 2.3 - 06/2014

2.1.2

Commissioning with the keypad

1. Switch on 24-V supply of the regenerative power supply module.

– With the first switch-on of the regenerative power supply module, the filter data are

automatically read out of the electronic filter nameplate (ENP) and temporarily

saved in the regenerative power supply module.

2. If the mains voltage is not 400/415 V, adapt the Lenze setting in

C00173

accordingly.

Note: A change of the setting in

C00173

also has an impact on the permissible device

utilisation! In the chapter "Rated data" of the Hardware Manual, the device types

and their permissible device utilisation at different mains voltages and switching

frequencies are specified.

3. Carry out optional parameter setting:

Parameterising the brake chopper/brake resistor

( 22)

Signal configuration

( 30)

4. Save the parameter set (

C00002

= "11: Save start parameters").

– By saving the parameter set, certain data such as the filter data are permanently

available in the regenerative power supply module and do not need to be read again

from the electronic filter nameplate at the next switch-on. This shortens the

initialisation time correspondingly.

5. Switch on mains voltage  the DC bus is charged.
6. Deactivate controller inhibit via controller enable terminal (RFR)  regenerative

feedback is enabled.

7.

Controlling the regenerative power supply module via terminals

.

( 19)