5 communication phases/network management, Communication phases/network management – Lenze E94ARNE Regenerative power supply User Manual

Page 107

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

107

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Communication phases/network management

6.5

Communication phases/network management

Regarding communication via the system bus, the device distinguishes between the

following states:

Tip!
In every state, the entire initialisation or parts of it can be restarted by transferring

the corresponding network management telegrams.

State

Explanation

"Initialisation"

Initialisation starts when the device is switched on.

• In this phase, the device does not take part in the bus data transfer.

• All CAN-relevant parameters are overwritten with their default values.

• After initialisation has been completed, the device is automatically set to

the "pre-operational" state.

"Pre-operational"

(before being ready for operation)

The device can receive parameter data. Process data are ignored.

"Operational"

(ready for operation)

The device can receive parameter data and process data!

"Stopped"

Only network management telegrams can be received.

Communication object

Initialisation

Pre-operational

Operational

Stopped

PDO

SDO

Sync

Emergency

Boot up

Network management (NMT)

Advertising