EDS94ARNExxxx EN 2.3 - 06/2014

L

281

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00126

C00126

C00129

C00130

C00131

C00132

Parameter | Name:

C00126 | CPU temp. warning threshold

Data type: UNSIGNED_32

Index: 24449

d

= 5F81

h

Temperature threshold for advance warning of CPU temperature on the control card

• The response to be initiate when the threshold is reached can be selected in

C00589

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

°C

85 70 °C

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00129 | Brake resistor value

Data type: INTEGER_32

Index: 24446

d

= 5F7E

h

Required for monitoring of the brake resistor temperature.

Parameterising the brake chopper/brake resistor

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

Ohm

500.0 180.0 Ohm

Read access  Write access  CINH  PLC STOP  No transfer

Scaling factor: 10

Parameter | Name:

C00130 | Rated power of brake resistor

Data type: INTEGER_32

Index: 24445

d

= 5F7D

h

Required for monitoring of the brake resistor temperature.

Parameterising the brake chopper/brake resistor

Setting range

(min. value | unit | max. value)

Lenze setting

0

W

800000 5600 W

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00131 | Therm. capacity brake resistor

Data type: INTEGER_32

Index: 24444

d

= 5F7C

h

Required for monitoring of the brake resistor temperature.

Parameterising the brake chopper/brake resistor

Setting range

(min. value | unit | max. value)

Lenze setting

0

kWs

100000 485 kWs

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00132 | Activation brake chopper

Data type: UNSIGNED_8

Index: 24443

d

= 5F7B

h

From software version V2.0 onwards

Setting the brake chopper activation

Selection list

(Lenze setting printed in bold)

Information

0 Overvoltage
1 Overvoltage + overcurrent
2 Overvolt. + overcur. + util.

Read access  Write access  CINH  PLC STOP  No transfer