0x00b20000 – Lenze E94ARNE Regenerative power supply User Manual

Page 254

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

254

L

EDS94ARNExxxx EN 2.3 - 06/2014

CAN module (MXI2) SDO client: Faulty configuration [0x00b20000]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: A

configuration error has occurred in the CAN SDP client.

• Faulty project download.

• Invalid SDO client settings according to DS301V402 in

the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.