9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Communication phases/network management

110

L

EDS94ARNExxxx EN 2.3 - 06/2014

6.5.3

Parameterising a device to act as a CAN master

If the initialisation of the system bus and the associated state change from "pre-

operational" to "operational" is not effected by a higher-level host system, the regenerative

power supply module can instead be defined to be a "quasi" master and execute this task.

C00352

serves to configure the CAN master functionality of the regenerative power supply

module.

Acting as the CAN master, the regenerative power supply module can change the

communication state of all nodes connected to the bus (broadcast telegram) to

"operational" by means of the NMT telegram "start remote node". Only this

communication state enables data exchange via process data objects.

C00378

serves to set a delay time, which has to expire after mains switching before the

regenerative power supply module puts the NMT telegram "start remote node" on the

bus.

Tip!
The master functionality is only required for the initialisation phase of the drive

system.

Parameter

Information

Lenze setting

Value Unit

C00352

CAN slave/master

Slave

C00378

CAN delay boot-up - Operational

3000 ms

Note!

A change in master/slave operation (

C00352

) will only become effective

• after power-on of the regenerative power supply module
OR
• if the NMT telegram "reset node" or "reset communication" is sent to the

regenerative power supply module.

As an alternative to the NMT telegram "reset node", the device command

C00002

= "91: CAN on-board: Reset node" can be used to reinitialise the CAN-

specific device parameters.