Safety module has been changed [0x00680018, Combination mxi1/mxi2 not possible [0x00680019, Firmware has been changed [0x0068001a – Lenze E94ARNE Regenerative power supply User Manual

Page 214: Memory module: faulty file system [0x0068001c, Firmware incompatible to control card [0x0068001e, 0x0068001f, 0x00680019, 0x0068001a, 0x0068001e, 0x0068001c

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

214

L

EDS94ARNExxxx EN 2.3 - 06/2014

Safety module has been changed [0x00680018]

Combination MXI1/MXI2 not possible [0x00680019]

Firmware has been changed [0x0068001a]

Memory module: Faulty file system [0x0068001c]

Firmware incompatible to control card [0x0068001e]

Combination memory module/device not possible [0x0068001f]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The safety module has been changed since the last

mains switching.

- (Only information or warning locked if the hardware

type has changed as well.)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The combination of the extension modules plugged into

the module slots MXI1 & MXI2 is not supported.

Use a permitted module combination.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The firmware of the operating system has been updated. - (Information only)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Memory module is plugged in incorrectly or is defective. • Plug in the memory module correctly.

• Exchange defective memory module.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Firmware is not compatible with the hardware.

Transfer the compatible firmware.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The memory module used is not supported by the

regenerative power supply module according to the

licence model.

Plug in supported memory module and switch the

mains.

• The regenerative power supply module only supports

the MM220 memory module (licence: Motion Control

HighLevel).