2 heartbeat protocol, Heartbeat protocol – Lenze E94ARNE Regenerative power supply User Manual

Page 140

Advertising
background image

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Monitoring

140

L

EDS94ARNExxxx EN 2.3 - 06/2014

6.9.2

Heartbeat protocol

The heartbeat protocol provides an alternative to the node guarding protocol for

monitoring nodes within a CAN network. In contrast to node guarding, this monitoring

method does not require polling by means of RTR telegrams (remote transmission request)

from the NMT master.

Schematic procedure

[6-10] Heartbeat protocol

1. A heartbeat producer cyclically sends a heartbeat telegram to one or more consumers.
2. The consumer(s) monitors/monitor the reception of the heartbeat telegram at regular

intervals.

Note!

Heartbeat and node guarding protocols may not be used simultaneously on a

CANopen device. When the heartbeat producer time is set > 0 ms, the heartbeat

protocol is used.

r: reserved (always 0)

s: state of the producer (0: boot-up, 4: stopped, 5: operational, 127: pre-operational)