Heatsink: thermal detector is defect [0x0077000a, Cpu: thermal detector is defect [0x0077000e, Heatsink: fan is defect [0x00770010 – Lenze E94ARNE Regenerative power supply User Manual

Page 223: 0x0077000e, 0x0077000d, 0x0077000c, 0x00770010, 0x0077000a, 0x0077000b, Diagnostics & fault analysis error messages

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

223

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

Heatsink: Thermal detector is defect [0x0077000a]

Inside the device: Thermal detector is defect [0x0077000b]

Filter: Thermal detector or fan is defect [0x0077000c]

DC-bus capacitor: Thermal detector is defect [0x0077000d]

CPU: Thermal detector is defect [0x0077000e]

Heatsink: Fan is defect [0x00770010]

Response (Lenze setting printed in bold)

Setting:

C00588

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for heatsink temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00588

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for interior temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00594

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for filter temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00588

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for capacitor temperature supplies undefined

values.

Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00588

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Encoder for CPU temperature supplies undefined values. Check control cabinet temperature, maybe it is too low.

Response (Lenze setting printed in bold)

Setting:

C00610

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Speed of heatsink fan too low, e.g. due to dirt.

Check/clean fan.