C00322 | can tpdox tx mode, C00323 | can rpdox rx mode, C00324 | can tpdox delay time – Lenze E94ARNE Regenerative power supply User Manual

Page 296: C00325 | service code, C00322/1, C00323/1, C00324/1, C00323/2, C00323/3, C00323/4

Advertising
background image

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00322

296

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00322

C00323

C00324

C00325

Parameter | Name:

C00322 | CAN TPDOx Tx mode

Data type: UNSIGNED_8

Index: 24253

d

= 5EBD

h

TPDO transmission mode according to DS301 V4.02

• Types 0 (acyclic sync), 1-240 (cyclic sync), 254 (event-controlled manufacturer-specific), 255 (event-controlled

device-profile-specific) are supported.

• The basic PDO setting is "254" (event-controlled).

• Mapping of CANopen objects

I-1800/2

...

I-1803/2

(see DS301 V4.02).

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Information

C00322/1

254

Transmission mode for TPDO1 ... TPDO4

C00322/...
C00322/4

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00323 | CAN RPDOx Rx mode

Data type: UNSIGNED_8

Index: 24252

d

= 5EBC

h

RPDO transmission mode according to DS301 V4.02

• Serves as monitoring setting for RPDOs in case of sync-controlled PDOs.

• Types 0 (acyclic sync), 1-240 (cyclic sync), 254 (event-controlled manufacturer-specific), 255 (event-controlled

device-profile-specific) are supported.

• The basic PDO setting is "254" (event-controlled).

• Mapping of CANopen objects

I-1400/2

...

I-1403/2

(see DS301 V4.02).

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

0

255

Subcodes

Lenze setting

Information

C00323/1

254

Transmission mode for RPDO1 ... RPDO4

C00323/...
C00323/4

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00324 | CAN TPDOx delay time

Data type: UNSIGNED_16

Index: 24251

d

= 5EBB

h

TPDO inhibit time according to DS301 V4.02

• Minimum time between the sending of two identical TPDOs.

• The delay time is entered in 1/10 ms and automatically rounded to full milliseconds by the code.

• Mapping of CANopen objects

I-1800/3

...

I-1803/3

(see DS301 V4.02).

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

0

1/10 ms

65535

Subcodes

Lenze setting

Information

C00324/1

0 1/10 ms

Delay time for TPDO1 ... TPDO4

C00324/...
C00324/4

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00325 | Service code

Data type: UNSIGNED_8

Index: 24250

d

= 5EBA

h

This code is used internally by the device and must not be overwritten by the user!