9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

Incorrect memory module [0x00680012]

Incorrect safety module [0x00680013]

Power stage has been changed [0x00680014]

MXI1: Module has been changed [0x00680015]

MXI2: Module has been changed [0x00680016]

Memory module has been changed [0x00680017]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The memory module is not supported by the operating

system.

• Use a different module.

• Please contact Lenze.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

A safety module is inserted in the regenerative power

supply module. The regenerative power supply module

does not support safety engineering.

Use SM0 safety module (without safety engineering).

• Then, restart the controller.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The power section has been changed since the last mains

switching.

- (Only information or warning locked if the hardware

type has changed as well.)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module in the module slot MXI1 has been

changed since the last mains switching.

- (Only information or warning locked if the hardware

type has changed as well.)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module in the module slot MXI2 has been

changed since the last mains switching.

- (Only information or warning locked if the hardware

type has changed as well.)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The memory module has been changed since the last

mains switching.

- (Only information or warning locked if the hardware

type has changed as well.)