Can on board" system bus parameter data transfer – Lenze E94ARNE Regenerative power supply User Manual

Page 131

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

131

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Parameter data transfer

Telegram 2 to the drive: request of the 1st data block

Response telegram 2 from the drive: transmission of 1st data block

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Data 1

Data 2

Data 3

Data 4

Data 5

Data 6

Data 7

0x060C

0x60

0x00

0x00

0x00

0x00

0x00

0x00

0x00

Explanations - telegram to drive
Command

= 0x60 = "read segment request" (request to read the data block)

• Bit 4 = 0 (toggle bit)
Influence of the toggle bit on the request command

The individual blocks are toggled in turn, i.e. first the request with the command "0x60" (=

0110*0000

bin

), then the one with the command "0x70" (= 0111*0000

bin

), then "0x60" again, etc.

* toggle bit

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Data 1

Data 2

Data 3

Data 4

Data 5

Data 6

Data 7

0x058C

0x00

0x30

0x31

0x2E

0x30

0x30

0x2E

0x30

0

asc

1

asc

.

asc

0

asc

0

asc

.

asc

0

asc

Explanations - telegram to drive
Command

= 0x00 = 00000000

bin

• Bit 4 = 0 (toggle bit)
Influence of the toggle bit on the transmission command

• The 1st response of the controller in the command byte is "0x0000*0000

bin

" if the bytes 2 ... 8

are completely filled with data and further telegrams will follow.

• The 2nd response of the controller in the command byte is "0x0001*0000

bin

" if the

bytes 2 ... 8 are completely filled with data and further telegrams will follow, etc.

* toggle bit

Data 1 ... 7

= "01.00.0" (ASCII representation)