2 ixt utilisation of brake transistor, Ixt utilisation of brake transistor – Lenze E94ARNE Regenerative power supply User Manual

Page 26

Advertising
background image

9400 regenerative power supply module | Parameter setting

Regenerative power supply module application

Parameterising the brake chopper/brake resistor

26

L

EDS94ARNExxxx EN 2.3 - 06/2014

3.1.3.2

Ixt utilisation of brake transistor
The regenerative power supply module monitors the Ixt utilisation of the internal brake

transistor.

[3-1]

Signal flow of Ixt utilisation - brake chopper

The monitoring function is based on a mathematical model which calculates the

braking current from the current DC-bus voltage and the brake resistance

parameterised.
– Hence, the monitoring function can respond even if no brake resistor is connected

and can therefore also be used for a testing mode to check the parameterisation.

The calculation considers the thermal utilisation of the brake transistor by a

correspondingly adapted time constant.

Use

C00133

to select whether the minimum brake resistance depending on the mains

setting in

C00173

(display in

C00134

), or the brake resistance value parameterised in

C00129

is to be used as a reference for calculating the utilisation.

C00137

displays the calculated utilisation of the brake transistor in [%].

– A 100 % utilisation corresponds to the continuous braking power which is provided

by the brake chopper at a DC-bus voltage of 790 V (or 390 V at a mains voltage of

230 V).

– The maximum braking power (assuming that the utilisation starts at 0 %) can be

provided for a period depending on the device.

– The calculated utilisation is also provided as the oscilloscope signal

Common.dnIxtBrakeChopper to check the braking operation while the system is

running
(scaling: 2

30

≡ 100 %).

If the utilisation exceeds the advance warning threshold set in

C00570

, the message

"Brake chopper: Ixt > C00570" is entered into the logbook and the response set in

C00569

(default setting: "Warning") is activated.

Note!

The braking operation will never be switched off by this monitoring function.

Ixt

C00137

1

0

C00134

C00129

C00133

T

= 0

Off

T

= 1

On

100 %

C00570

C00569

C00573

Logbook entry "Brake chopper: Ixt > C00570"

Logbook entry "

"

Brake chopper: Ixt overload

U

DC_act

U

DC_act

I

=

Br

I

=

Br

I

Br

= f(duty cycle, R )

Br

Advertising