9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

Read error service register [0x00720000]

External error [0x00750000]

Device enabled [0x00750001]

Device: Pulse inhibit is active [0x00750005]

PLC configuration invalid [0x00750006]

Heatsink: Temperature > C00122 [0x00770000]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An error has occurred while reading from or writing to

the service register.

Mains switching

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

Setting:

C00581

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The drive interface has activated the error message

"External error".

• Check external device to be monitored.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The regenerative power supply module is enabled and is

in the "Operation" device state.

- (Information only)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Pulse inhibit is active in the regenerative power supply

module.

- (Information only)

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

An invalid control configuration has occurred.

Load another application.

Response (Lenze setting printed in bold)

Setting:

C00582

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Heatsink temperature higher than variable limit

temperature (

C00122

).

• Ambient device temperature too high.

• Dirty fan or ventilation slots.

• Value set under C00122 is too low.

• Check control cabinet temperature.

• Clean filter.

• Clean regenerative power supply module.

• Set a higher value under

C00122

.