Can module (mxi2): bus off [0x00ac0000, 0x00a30000, 0x00a20000 – Lenze E94ARNE Regenerative power supply User Manual

Page 249: 0x00ac0000, 0x00ac0001, Diagnostics & fault analysis error messages

Advertising
background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

249

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

CAN module (MXI1) SDO server: Faulty configuration [0x00a20000]

CAN module (MXI1) SDO client: Faulty configuration [0x00a30000]

CAN module (MXI2): Bus off [0x00ac0000]

CAN module (MXI2): Invalid node address 0 [0x00ac0001]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: A

configuration error has occurred in the CAN SDP server.

• Faulty project download.

• Invalid SDO server settings according to DS301V402

in the Engineer or PLC Designer.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: A

configuration error has occurred in the CAN SDP client.

• Faulty project download.

• Invalid SDO client settings according to DS301V402 in

the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

Setting:

C14595

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: "Bus-off"

state

• Too many faulty telegrams received.

• Defective cable (e.g. loose contact).

• Two nodes with the same ID.

• Eliminate disturbances (e.g. EMC).

• Remove loose contact, screw down adapter.

• Assign different node IDs.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI2: Initialisation

error

• The hardware assignment of the node address has

been selected via DIP switch and the DIP switches for

the node address are set to zero.

• Note: Instead of the impermissible node address 0 the

node address 1 is used.

• Set the DIP switches to a node address unequal 0 and

restart the controller.

• Activate the node address assignment by means of

software by changing the position of DIP switch 2 and

restart the controller.