EDS94ARNExxxx EN 2.3 - 06/2014

L

39

9400 regenerative power supply module | Parameter setting

Device interface

Device commands

4.1.1

Load Lenze setting

The

C00002

= "0: Load Lenze setting" device command can be used to reset the parameters

of the active application to the Lenze setting which is stored in the firmware of the

regenerative power supply module:

[4-1]

"Load Lenze setting" function

Only possible when the controller is inhibited and the application has been stopped.

All parameter changes made since the last saving of the parameter set will get lost!

This device command only has an impact on the settings of the operating system,

application, and module parameters, the active application remains unchanged.

Possible status displays for this device command

Related device commands

Load start parameters

( 40)

Save start parameters

( 44)

Application 3

PS

Application 2

PS

Memory module MM

PS

9400

PS

RAM

Firmware

Application 1

Application

PS

Status (

C00003

)

Meaning

34050 Device command in process

0 Device command executed successfully

1 General fault

39424 CAN fault

... ...

39679 CAN fault