9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Monitoring

Life guarding event
The "life guarding event" is triggered in the NMT slave if the slave has not received an RTR

telegram from the NMT master within the "node life time":

In the Lenze setting, the NMT slave changes from the "operational" to the "pre-

operational" communication state.
– Another state change can be set in

C00625

or via the

I-1029

object.

An emergency telegram with the emergency error code 0x8130 is sent to the NMT

master.

The response set in

C00614

is initiated (Lenze setting: "No response").

Node guarding event
The "node guarding event" is triggered in the NMT master if the master has not received a

response from the NMT slave to the RTR telegram within the "node life time" or if the

toggle bit in the response telegram has not changed within the "node life time":

In the Lenze setting, the NMT master changes from the "operational" to the "pre-

operational" communication state.
– Another state change can be set in

C00625

or via the

I-1029

object.

The response set in

C00612/1...32

is initiated (Lenze setting: "No response"). For each

node to be monitored an individual response can be set in the NMT master.

Note!

The "life guarding event" can only be triggered in the NMT slave if at least one

RTR telegram from the NMT master has been received successfully.

Note!

The "node guarding event" can only be triggered in the NMT master if at least

one response from the requested NMT slave has been received successfully.