3 read block parameters, Read block parameters – Lenze E94ARNE Regenerative power supply User Manual

Page 130

Advertising
background image

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Parameter data transfer

130

L

EDS94ARNExxxx EN 2.3 - 06/2014

6.7.3.3

Read block parameters
Task: The firmware version (code C00099) is to be read from the parameter set of the

controller with node address "12". The firmware version has a length of 11 ASCII characters

and is transferred as a block parameter. Within the user data, each block occupies the data

width from the 2nd to the 8th byte.

Telegram 1 to the drive: read request

Response telegram 1 from the drive: specification of the block length (11 characters)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x060C

0x40

0x9C

0x5F

0x00

0x00

0x00

0x00

0x00

Explanations - telegram to drive
Identifier

= 1536 + node address = 1536 + 12 = 1548 = 0x060C

(1536 = basic identifier of SDO1 to the controller)

Command

= 0x40 = "read request" (request to read a parameter from the controller)

Index

= 24575 - code number = 24575 - 99 = 24476 = 0x5F9C

Subindex

= 0 (code C00099 has no subcodes)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x058C

0x41

0x9C

0x5F

0x00

0x0B

0x00

0x00

0x00

Explanations - telegram from drive
Identifier

= 1408 + node address = 1408 + 12 = 1420 = 0x058C

(1408 = basic identifier of SDO1 from the controller)

Command

= 0x41 = "read response" (the response is a block telegram)

Index

Same as for telegram to the drive

Subindex
Data 1 ... 4

= 0x0000000B = data length of 11 characters in the ASCII format