Can on board: bus-off [0x00830000, Can on board: invalid node address 0 [0x00830001, 0x00830002 – Lenze E94ARNE Regenerative power supply User Manual

Page 232: 0x00830000, 0x00830001, 0x007f0004, Diagnostics & fault analysis error messages

Advertising
background image

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

232

L

EDS94ARNExxxx EN 2.3 - 06/2014

Communication with module in MXI2 interrupted [0x007f0004]

CAN on board: bus-off [0x00830000]

CAN on board: Invalid node address 0 [0x00830001]

CAN on board: Basic configuration invalid [0x00830002]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

It is not possible to establish communication between

the regenerative power supply module and the

extension module in the MXI2 module slot.

• Switch off regenerative power supply module, insert

extension module correctly in module slot MXI2, and

switch on the regenerative power supply module

again.

• If the problem occurs again, replace the extension

module.

Response (Lenze setting printed in bold)

Setting:

C00595

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: "Bus off" state

• Too many faulty telegrams received.

• Defective cable (e.g. loose contact).

• Two nodes with the same ID.

• Eliminate disturbances (e.g. EMC).

• Remove loose contact, screw down adapter.

• Assign different node IDs.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: initialisation error

• The hardware assignment of the node address has

been selected via DIP switch and the DIP switches for

the node address are set to zero.

• Note: Instead of the impermissible node address 0 the

node address 1 is used.

• Set the DIP switches to a node address unequal 0 and

restart the controller.

• Activate the node address assignment by means of

software by changing the position of DIP switch 2 and

restart the controller.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: configuration error

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.