4 state "operation, 5 state "warning active, 6 state "warning locked active – Lenze E94ARNE Regenerative power supply User Manual

Page 82: 7 state "trouble active, State "operation, State "warning active, State "warning locked active, State "trouble active

Advertising
background image

9400 regenerative power supply module | Parameter setting

Device interface

Device states

82

L

EDS94ARNExxxx EN 2.3 - 06/2014

4.2.4

State "Operation"

This is the device state of the regenerative power supply module during operation.

4.2.5

State "Warning active"

This state can occur simultaneously to the device states "Device is ready to switch on",

"Device is switched on" and "Operation" if a monitoring function responds for which the

error response "Warning" has been parameterised.

4.2.6

State "Warning locked active"

This state can occur simultaneously to the device states "Device is ready to switch on",

"Device is switched on" and "Operation" if a monitoring function responds for which the

error response "Warning locked" has been parameterised.

4.2.7

State "Trouble active"

This device state becomes active as soon as a monitoring function responds for which the

error response "Trouble" has been parameterised.

The device state is automatically exited when the error cause has been eliminated:
– "Trouble active" state < 500 ms: return to the original device state.
– "Trouble active" state > 500 ms: return via the device state "Device is ready to switch

on".

LED DRIVE READY

LED DRIVE ERROR

Display in

C00183

OFF

0: Operation

LED DRIVE READY

LED DRIVE ERROR

Display in

C00183

1: Operation/Warning active

LED DRIVE READY

LED DRIVE ERROR

Display in

C00183

2: Operation/Warning locked act.

LED DRIVE READY

LED DRIVE ERROR

Display in

C00183

OFF

104: Trouble active