9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list

272

L

EDS94ARNExxxx EN 2.3 - 06/2014

10.2

Parameter list

This chapter describes all parameters of the operating system in numerically ascending

order.

C00002

Note!

The parameter descriptions are based on software version V2.

Parameter | Name:

C00002 | Device commands

Data type: UNSIGNED_32

Index: 24573

d

= 5FFD

h

Device commands

C00003

shows the state of the last executed device command.

• Under

C00150

you can query the current state of the device control.

Note:

Before switching off the supply voltage after a device command has been executed, check via the status display in

C00003

that the device command has been executed successfully!

The meaning of the status display in

C00003

can be obtained from the subchapter for the corresponding device

command in the "

Device commands

" chapter.

Selection list

(Lenze setting printed in bold)

Information

0 Load Lenze setting

Resets parameters to Lenze setting.

• Only possible when the controller is inhibited and the

application has been stopped.

1 Load start parameters

Loads parameters from the memory module.

• Only possible when the controller is inhibited and the

application has been stopped.

2 ENP: Load route data

Reads plant data from the electronic filter nameplate.

• Only possible when the controller is inhibited and the

application has been stopped.

5 Activate application

Activates the application selected under

C00005

.

• Whether the application is also started, depends on

the auto-start setting selected.

• Only possible when the application has been stopped.

7 Save selected application

Selects the active application as start application.

11 Save start parameters

Saves parameters fail-safe in the memory module.

20 Delete logbook

Deletes all logbook entries.

21 Archive log file

Exports logbook entries to file.

31 Start application
32 Stop application
33 Reset program

Executes a reset.

• All variables are reset to their initialisation values.

• The situation corresponds to the start of a new

program loaded into the control system (cold start).

34 Delete program

Executes a reset (original).

• All variables are reset to their initialisation values.

• The application program is deleted and the

regenerative power supply module is reset to its

original state.