9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

Combination of module in MXI1/device not possible [0x00680020]

Combination of module in MXI2/device not possible [0x00680021]

Code Refresh [0x00690000]

Internal error (memory area - logbook) [0x00690001]

Internal error (LDS instance data) [0x00690002]

Internal error (LDS tasks) [0x00690003]

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module in module slot MXI1 is not

supported by the regenerative power supply module.

• Remove the extension module and switch the mains.

• Plug in supported extension module and switch the

mains.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The extension module in module slot MXI2 is not

supported by the regenerative power supply module.

• Remove the extension module and switch the mains.

• Plug in supported extension module and switch the

mains.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Serious device error or component failure.

Switch off regenerative power supply module, and then

switch it on again.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Serious device error or component failure.

Switch off regenerative power supply module, and then

switch it on again.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Serious device error or component failure.

Switch off regenerative power supply module, and then

switch it on again.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

Serious device error or component failure.

Switch off regenerative power supply module, and then

switch it on again.

• Please contact Lenze if the problem occurs again.