1 process data object identifiers, Process data object identifiers – Lenze E94ARNE Regenerative power supply User Manual

Page 112

Advertising
background image

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Process data transfer

112

L

EDS94ARNExxxx EN 2.3 - 06/2014

6.6.1

Process data object identifiers

In the Lenze setting, the identifier for the process data objects PDO1 ... PDO4 consists of a

basic identifier and the node address set in

C00350

:

Identifier (COB-ID) = basic identifier + node address (node ID)

In the Lenze setting, the basic identifiers of the PDOs are preset according to the

"Predefined Connection Set" of DS301 V4.02.

The PDO identifier settings can be changed via the Lenze codes and CANopen indexes

listed in the following table. In this way, you can also set an identifier independent of

the node address for certain PDOs.

Tip!
The "Predefined Connection Set" can always be restored via the following device

commands (

C00002

):

• "93: CAN on-board: Pred.Connect.Set" for on-board CAN
• "94: CAN module: Pred.Connect.Set" for communication module E94AYCCA

Process data object

Basic identifier

Individual setting

dec

hex

Lenze code

CANopen index

PDO1

RPDO1

512

0x200

C00321/1

I-1400/1

TPDO1

384

0x180

C00320/1

I-1800/1

PDO2

RPDO2

768

0x300

C00321/2

I-1401/1

TPDO2

640

0x280

C00320/2

I-1801/1

PDO3

RPDO3

1024

0x400

C00321/3

I-1402/1

TPDO3

896

0x380

C00320/3

I-1802/1

PDO4

RPDO4

1280

0x500

C00321/4

I-1403/1

TPDO4

1152

0x480

C00320/4

I-1803/1

Note!

When the node address has been changed (

C00350

) and CAN reset node is

executed subsequently, the subcodes of

C00320

and

C00321

are automatically

set to the identifiers resulting from the respective basic identifier and the node

address set.