9400 regenerative power supply module | Parameter setting

I/O terminals

Digital inputs

94

L

EDS94ARNExxxx EN 2.3 - 06/2014

5.4

Digital inputs

The regenerative power supply module is equipped with 8 freely configurable digital

inputs.

Control input RFR of terminal strip X5 for controller enable is permanently connected

to the device control.

5.4.1

Terminal assignment/electrical data

5.4.2

Parameter setting

Short overview of parameters for the digital inputs:

Terminal

Use

Electrical data

X5/DI1

X5/DI8

Digital input 1 ... 8

LOW level: 0 ... +5 V

HIGH level: +15 ... +30 V

Input current: 8 mA per input

(at 24 V)

Interference-voltage-

proof:

max. ±30 V

Conversion rate: 1 kHz

X5/RFR

Controller enable

See digital inputs

X5/GI

Reference potential (digital ground)

X5

GI

RFR

DI1

DI2

DI3

DI4

DI5

DI6

DI7

DI8

Parameter

Information

C00114

Dig. input x: Terminal polarity

C00443

Status: Digital inputs

C02803

Status word: Digital inputs

C02830

Digital inputs: Delay time

Highlighted in grey = display parameter