9400 regenerative power supply module | Parameter setting

Device interface

Device commands

4.1.31

Activate parameter sets 1 ... 4

In addition to the start parameters, up to four more parameter sets can be stored in the

memory module for each application. This, for instance, serves to define different

controller settings for an application, which can then be simply activated via device

command.
The following device commands can be used to activate parameter sets 1 ... 4 for the active

application (if available on the memory module):

C00002

= "201: Activate parameter set 1"

C00002

= "202: Activate parameter set 2"

C00002

= "203: Activate parameter set 3"

C00002

= "204: Activate parameter set 4"

[4-9]

Example: "Activate parameter set 1" function

Only possible when the controller is inhibited and the application has been stopped.

All parameter changes made since the last saving of the previously active parameter

set will get lost!

These device commands only have an impact on the settings of the operating system,

application, and module parameters, the active application remains unchanged.

* In this example application 1 is the active application

PS 4

PS 3

PS 2

Application 2

PS 1

PS

PS 4

PS 3

PS 2

Memory module MM

PS

9400

PS

RAM

Firmware

Application 1*

Application 1*

PS