CAN module (MXI1) RPDO6: Telegram not received or faulty [0x00a10005]

CAN module (MXI1) RPDO7: Telegram not received or faulty [0x00a10006]

CAN module (MXI1) RPDO8: Telegram not received or faulty [0x00a10007]

CAN module (MXI1) PDO manager: Faulty configuration [0x00a10008]

Response (Lenze setting printed in bold)

Setting:

C13591/6

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 6

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C13591/7

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 7

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

Setting:

C13591/8

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-IN 8

error

• Incorrect PDO telegram length.

• Transmission error.

• PDO time monitoring has responded.

• Set the correct telegram length for the CAN master

(sender).

• Eliminate disturbances in the environment (e.g. EMC).

• Select a different monitoring time or switch off time

monitoring.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CANopen communication module in MXI1: CAN-PDO

configuration error

• Faulty project download.

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Mapping variables have incorrect CANopen indexes

according to DS405.

• Repeat download.

• Correct CAN settings in the project and regenerate

project.