9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00357

C00357

C00359

Parameter | Name:

C00357 | CAN RPDOx monitoring time

Data type: UNSIGNED_16

Index: 24218

d

= 5E9A

h

Mapping of RPDO event time (see DS301 V4.02)

• With a value unequal "0", the RPDO will be expected after the set time.

• If the RPDO is not received within this time, a parameterisable error message can be activated.

"CAN on board" system bus

Setting range

(min. value | unit | max. value)

0

ms

65535

Subcodes

Lenze setting

Information

C00357/1

3000 ms

Monitoring time for RPDO1 ... RPDO4

C00357/...
C00357/4

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00359 | CAN status

Data type: UNSIGNED_8

Index: 24216

d

= 5E98

h

"CAN on board" system bus

Selection list

(display only)

0 Operational
1 Pre-operational
4 Boot up
5 Stopped
7 Reset
8 Initialisation
9 Unknown

10 Baud rate autom. detected

Read access  Write access  CINH  PLC STOP  No transfer