C00114 | dig. input. x: terminal polarity, C00118 | dig. output. x: terminal polarity, C00121 | filter temp. warning threshold – Lenze E94ARNE Regenerative power supply User Manual

Page 280: C00122 | heatsink temp. warn. threshold, C00123 | warning threshold device util, C00123, Exceeds the warning threshold set in, C00114, C00118, C00121

Advertising
background image

9400 regenerative power supply module | Parameter setting

Parameter reference

Parameter list | C00114

280

L

EDS94ARNExxxx EN 2.3 - 06/2014

C00114

C00118

C00121

C00122

C00123

Parameter | Name:

C00114 | Dig. input. x: Terminal polarity

Data type: UNSIGNED_8

Index: 24461

d

= 5F8D

h

"0" = positive logic (HIGH level = TRUE, LOW level = FALSE)

"1" = negative logic (HIGH level = FALSE, LOW level = TRUE)
Setting range

(min. value | unit | max. value)

0

1

Subcodes

Lenze setting

Information

C00114/1

0

Terminal polarity - digital input 1 ... 8

C00114/...
C00114/8

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00118 | Dig. output. x: Terminal polarity

Data type: UNSIGNED_8

Index: 24457

d

= 5F89

h

"0" ≡ positive logic (TRUE ≡ HIGH level, FALSE ≡ LOW level)

"1" ≡ negative logic (FALSE ≡ HIGH level, TRUE ≡ LOW level)
Setting range

(min. value | unit | max. value)

0

1

Subcodes

Lenze setting

Information

C00118/1

0

Terminal polarity - digital output 1 ... 4

C00118/...
C00118/4

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00121 | Filter temp. warning threshold

Data type: UNSIGNED_32

Index: 24454

d

= 5F86

h

Temperature threshold for filter temperature advance warning

• The response to be initiated when the threshold is reached can be selected in

C00584

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

°C

150 135 °C

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00122 | Heatsink temp. warn. threshold

Data type: UNSIGNED_32

Index: 24453

d

= 5F85

h

Temperature threshold for heatsink temperature advance warning

• The response to be initiated when the threshold is reached can be selected in

C00582

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

°C

85 85 °C

Read access  Write access  CINH  PLC STOP  No transfer

Parameter | Name:

C00123 | Warning threshold device util.

Data type: UNSIGNED_32

Index: 24452

d

= 5F84

h

Adjustable threshold for I x t advance warning

• The advance warning is sent if the device utilisation (

C00064

) is higher than the set threshold.

• The response to be initiated when the threshold is reached can be selected in

C00604

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

100 90 %

Read access  Write access  CINH  PLC STOP  No transfer