EDS94ARNExxxx EN 2.3 - 06/2014

L

153

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

I-1014

If a communication error or an internal error of the communication module or the

regenerative power supply module occurs or is acknowledged (e.g. "trouble"), an error

message is sent on the system bus. For every error, the telegram is sent once. Bit 31 can be

used to activate or deactivate this function.

This object is related to the Lenze code

C00391

.

[6-7]

Assignment of the data telegram

I-1015

Time which must elapse after the transmission of an error message (

I-1014

) before further

error messages can be sent on the system bus.

The entered value multiplied by 0.1 gives the delay time in [ms]. The values are

automatically rounded up to whole values in [ms].

This object is related to the Lenze code

C00392

.

Index:

I-1014

Name:

COB-ID EMCY

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: COB-ID EMCY

0x80 + node ID

0

4294967295 rw

U32

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0/1

0

Extended identifier*

11-bit identifier

* The extended identifier is not supported - bits 11 ... 29 must be set to "0".

Bit

Setting

Bit 31

0 Emergency object valid.
1 Emergency object invalid.

Note!

The identifier can only be changed in the "emergency object invalid" state

(Bit 31 = 1).

Index:

I-1015

Name:

Inhibit time EMCY

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Inhibit time EMCY

0

0

0.1 ms

65535 rw

U32